GARAN EWS-102 Impostazione del sistema - Pagina 2

Sfoglia online o scarica il pdf Impostazione del sistema per Unità di controllo GARAN EWS-102. GARAN EWS-102 4.
Anche per GARAN EWS-102: Impostazione del sistema (4 pagine), Impostazione del sistema (4 pagine), Calibrazione e impostazione (8 pagine), Informazioni supplementari (2 pagine)

GARAN EWS-102 Impostazione del sistema
EWS-102 CONTROL UNIT
To begin the system setup
press the
and
buttons together
Press the
Press the
The instrument then counts down from 10 to 1 to allow �me for the operator to ensure that the
Countdown
elevator cabin is empty
The "Zero" point has now been calibrated and stored.
CAL indicates that the calibra�on is now complete (remains for 10 seconds)
Press the
Mul� Analog version only: See note 3 page 1. A�er the EWS 102 calibra�on and setup has been
completed, place the the li� at the lowest floor level and rezero following the process on this page, this
will finalise the Analog output calibra�on.
Firmware 5.5 Rev 2 Booklet subject to alteration
bu�on to enter the zero calibra�on menu
bu�on
bu�on within 10 seconds to proceed to the Load Calibra�on
CALIBRATION ZERO
www.garan.co.uk
www.garan.co.uk
Page 2