AirGorilla PCO/UV N-Duct Manuale dell'installatore - Pagina 4
Sfoglia online o scarica il pdf Manuale dell'installatore per Pulitore d'aria AirGorilla PCO/UV N-Duct. AirGorilla PCO/UV N-Duct 8.
Anche per AirGorilla PCO/UV N-Duct: Manuale d'uso (6 pagine)
SPECIFICATIONS
Dimensions
• Mounting Plate: 7" x 13"
• PCO Filter: 11" x 17"
• UV Lamp: 1.75" x 16.25"
• Duct mounting hole: 5" x 11"
Weight
• Complete Unit: 4 lbs.
Electrical
• 120V-277V, 50/60Hz
• Powercord - 9 ft., 3 prong,
rated to 240V
• UL Listed Electronic Ballast
UV Lamp
• 36 watt, 105 w/cm
Material
• Mounting Plate and Enclosure -
Fire Retardant ABS
INSTALLATION
IMPORTANT
This unit must be installed in compliance and in accordance with all national,
state, and local electrical and mechanical codes. Failure to do so will void all
expressed or implied warranty representations.
The PCO/UV N-Duct™ unit is designed for air disinfection and installs into the air handling
system or ductwork. Select a mounting location that offers sufficient space for the mounting
plate 7" x 13" and enough internal space for the UV lamps and PCO filter 11" H x 17" D. In
addition, allow for sufficient space for removal (pulling out) of an 18" UV lamp. Installation
also requires access to 120 – 277 VAC electrical power.
• Do not install where UV lamp is visible
• Do not expose wiring or plastic to UV light
• If installed near an air filter, check with the filter manufacturer for UV properties & safety.
2
@1 mtr.
• Do not install in outdoor applications
• Do not install beneath a humidifier
3