AB Quality PowerFlex 400 Frames D-H Bollettino di servizio - Pagina 4
Sfoglia online o scarica il pdf Bollettino di servizio per Controllore AB Quality PowerFlex 400 Frames D-H. AB Quality PowerFlex 400 Frames D-H 12. Main control board
4
PowerFlex 400 Frames D-H Replacement Procedure for Main Control Board
Removing and Locking Out
Power
Opening the Drive
Publication 22C-SB003A-EN-P – August 2008
If the drive is in service, do the following.
1. Turn off and lock out all incoming power to the drive. Wait five minutes.
L1
L2
L3
2. Verify that there is no voltage at the input power terminals.
ATTENTION: To avoid an electric shock hazard, verify that the
!
voltage on the bus capacitors has discharged before performing
any work on the drive. Wait five minutes for the capacitors to
discharge. Then, measure the DC bus voltage at the DC- and
DC+ terminals or at the DC- and P2 terminals on the power
terminal block. The voltage must be zero.
A darkened LCD display and LEDs are not an indication that
capacitors have discharged to safe voltage levels.
Frame D Drives
1. Loosen the two captive cover screws.
2. Pull the bottom of the cover out and up to release.
I
O