AB Quality PowerFlex 400 Frames D-H 서비스 게시판 - 페이지 4
{카테고리_이름} AB Quality PowerFlex 400 Frames D-H에 대한 서비스 게시판을 온라인으로 검색하거나 PDF를 다운로드하세요. AB Quality PowerFlex 400 Frames D-H 12 페이지. Main control board
4
PowerFlex 400 Frames D-H Replacement Procedure for Main Control Board
Removing and Locking Out
Power
Opening the Drive
Publication 22C-SB003A-EN-P – August 2008
If the drive is in service, do the following.
1. Turn off and lock out all incoming power to the drive. Wait five minutes.
L1
L2
L3
2. Verify that there is no voltage at the input power terminals.
ATTENTION: To avoid an electric shock hazard, verify that the
!
voltage on the bus capacitors has discharged before performing
any work on the drive. Wait five minutes for the capacitors to
discharge. Then, measure the DC bus voltage at the DC- and
DC+ terminals or at the DC- and P2 terminals on the power
terminal block. The voltage must be zero.
A darkened LCD display and LEDs are not an indication that
capacitors have discharged to safe voltage levels.
Frame D Drives
1. Loosen the two captive cover screws.
2. Pull the bottom of the cover out and up to release.
I
O