CP Electronics MWS3A-DD Manuale del prodotto - Pagina 10

Sfoglia online o scarica il pdf Manuale del prodotto per Sensori di sicurezza CP Electronics MWS3A-DD. CP Electronics MWS3A-DD 12. Direct dim microwave presence/absence detector
Anche per CP Electronics MWS3A-DD: Manuale di installazione (20 pagine)

CP Electronics MWS3A-DD Manuale del prodotto
10.3 Two channel, common switch (continued)
PLEASE NOTE THAT THE
DIMMING SIGNAL IS USED TO
SWITCH THE DIMMING
LUMINAIRE ON/OFF AND
THEREFORE THE 240V FEED
TO THE LUMINAIRE FITTING
MUST COME FROM THE
PERMANENT LIVE SUPPLY
NEUTRAL
LIVE
CIRCUIT PROTECTION
(IF REQUIRED)
10.4 Single channel switching
Functions: Switches channel 1 only with occupancy, optional override switch. No dimming output.
Configured to presence detection: Turns on automatically with occupancy. Press and release down
switch to turn off. Press and release up switch to turn back on. Turns off after occupancy.
Configured to absence detection: Press and release up switch to turn on. Press and release down
switch to turn off. Turns off after occupancy.
Channel mode: Set to ―Switch only‖
Switch mode: Set to ―2 position switch together‖. Note: a single position switch can be used instead to
toggle the output, set to ―1 position switch separate‖.
NEUTRAL
LIVE
CIRCUIT PROTECTION
(IF REQUIRED)
page 10
N
DIM-
L/OUT
DIM+
L
SW1/UP
SW2
DOWN
EBDSPIR-DD SENSOR
MWS3A-DD SENSOR
PLEASE NOTE THAT THE CENTRE BIASED RETRACTIVE
SWITCH WILL PROVIDE CONTROL FOR THE DIMMING
LUMAIRE(S) ONLY. THE NON-DIMMING LUMINAIRE(S) WILL
BE CONTROLLED ONLY BY THE SENSOR
N
DIM-
L/OUT
DIM+
L
SW1/UP
SW2
DOWN
EBDSPIR-DD SENSOR
MWS3A-DD SENSOR
DIMMING
BALLAST
LUMINAIRE
DIMMING LUMINAIRE
(NON-DIMMING)
CENTRE BIASED
RETRACTIVE SWITCH
(240V SWITCHING)
Optional for presence,
mandatory for absence detection
(NON-DIMMING)
CENTRE BIASED
RETRACTIVE SWITCH
(240V SWITCHING)
Optional for presence,
mandatory for absence detection
(DSI or DALI)
LUMINAIRE