ABB Contrac RSD 200-5,0 Manuale di istruzioni - Pagina 10
Sfoglia online o scarica il pdf Manuale di istruzioni per Controllore ABB Contrac RSD 200-5,0. ABB Contrac RSD 200-5,0 18. Electrical linear actuators for continuous modulating control
9.5 Mounting the actuator to the valve
- Completely retract the actuator thrust rod and put the actuator on the valve yoke.
- Make sure the valve stem is centrically aligned with the bore and at right angles to the actuator seat
(permissible parallel deviation < 0.1 mm referred to total stroke).
- Fasten the actuator to the yoke with screws of property class 8.8 (tensile strength 800 N|mm
strength 640 N/mm
- Use the handhweel to extend the thrust rod, link the rod with the valve stem via the clutch.
- Manually retract the thrust rod to check whether or not the external stop of the actuator is on the
housing flange before the valve cone gets in touch with the cover.
- If required, adjust with the clutch (only possible within certain limits!)
Fig. 7: Mounting RSD ... (example)
10
2
)
thrust rod hood
thrust rod hood
cover screw for
limit stop adjustment
thrust rod
mechanical
position indicator
servomotor
handwheel
handwheel release
fastening screws (8.8)
external limit stop
coupling
valve stem
valve yoke
valve
(r00158e1)
2
; yield