CREE LIGHTING SmartCast Manuale d'uso - Pagina 8
Sfoglia online o scarica il pdf Manuale d'uso per Apparecchiature di illuminazione CREE LIGHTING SmartCast. CREE LIGHTING SmartCast 8. Dynamic skylight
Anche per CREE LIGHTING SmartCast: Manuale di avvio rapido (20 pagine)

No Dimmer in group - Auto On,
Auto Off
Occupied Level
Occupied Level
100%
Unoccupied
Unoccupied
0%
Level
Level
Occupancy
Occupancy
HIGH
Sensitivity
Sensitivity
Occupancy
Occupancy
20 minutes
Timeout
Timeout
Minimum
Minimum
5%
Daylighting Level
Daylighting Level
Verify occupancy sensors.
Verify occupancy sensors.
To test that each sensor is functioning properly, select "Test Occupancy" mode from the Configuration Tool.
You will be prompted to select the occupancy group you want to test, at which point the group will enter a test
mode where each fixture within the group acts only on its own motion sensor and is assigned a 30-second
timeout. While the fixtures remain in this mode, you will verify that each fixture times out after approximately 30
seconds on no motion, remains off for a brief period of time (e.g., 30 seconds to 1 minute of no motion), and
then turns on again due to motion events detected by the fixture.
Once all occupancy sensors in the group have been verified, select "OK"
a problematic fixture (e.g., it won't time out or triggers falsely), you can adjust sensitivity for the group using the
Configuration Tool, under Device Settings → Occupancy → Set Sensitivity.
Device Settings → Occupancy → Set Occupied Level
Device Settings → Occupancy → Set Unoccupied
Level
Device Settings → Occupancy → Set Sensitivity
Device Settings → Occupancy → Set Timeout
Device Settings → Daylighting → Set Min Level
"OK" on the Configuration Tool. If you identify