Installation & Operation
3.1 Notes on installation
Supply voltage
When the supply voltage is connected to the power plug, all LEDs flash briefly for a moment.
The POWER LED lights up as soon as voltage is present.
You can supply the device with power via the Ethernet cable. In this case, the power plug
must be tightly sealed to prevent moisture from penetrating. The device is a class 0 device
according to PoE.
NOTICE
No simultaneous supply voltage
Do not supply the device with power through the mains and the PoE connection at the
same time.
Check whether the rated voltage of the power supply corresponds to the values in the
section "Technical specifications (Page 21)".
Safety extra low voltage
The equipment is designed for operation with Safety Extra-Low Voltage (SELV) by a
Limited Power Source (LPS). (This does not apply to 100 V...240 V devices.)
This means that only SELV / LPS complying with IEC 60950-1 / EN 60950-1 / VDE 0805-1
must be connected to the power supply terminals, or the power supply unit for the
equipment power supply must comply with NEC Class 2, as described by the National
Electrical Code (r) (ANSI / NFPA 70).
16
CAUTION
Operating Instructions, 06/2020, C79000-G8976-C515-03
SIMATIC RTLS4030G