Siemens SITRANS RD500 Manuale di istruzioni per l'uso - Pagina 4

Sfoglia online o scarica il pdf Manuale di istruzioni per l'uso per Interruttore Siemens SITRANS RD500. Siemens SITRANS RD500 8. Configuring sitrans rd500 for connection to multiranger with modbus rtu
Anche per Siemens SITRANS RD500: Manuale di istruzioni per l'uso (48 pagine), Manuale di istruzioni per l'uso (8 pagine), Manuale di istruzioni per l'uso (8 pagine), Manuale di applicazione (6 pagine), Manuale (11 pagine), Esempi di applicazione (9 pagine)

Siemens SITRANS RD500 Manuale di istruzioni per l'uso
GENERAL SPECIFICATIONS (CONT'D)
3. MEMORY: Non-volatile memory retains all programmable parameters. RD500
also stores the parameters in order to reprogram modules that are replaced.
4. ISOLATION LEVEL: 500 Vrms @ 50/60 Hz for 1 minute between the Signal Inputs
and the RD500 Power Supply Input.
5. COMMUNICATIONS: Provided by the RD500
6. CERTIFICATIONS AND COMPLIANCES:
SAFETY
UL508, CSA C22.2 No. 14-M05, UL61010-1, CAN/CSA C22.2 No. 61010-1 and
ANSI/ISA 12.12.01-2007, CSA 22.2 No. 213-M1987
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment for
measurement, control, and laboratory use, Part 1.

ELECTROMAGNETIC COMPATIBILITY

Emissions and Immunity to EN 61326: 2006: Electrical Equipment for
Measurement, Control and Laboratory use.
Electrostatic discharge
EN 61000-4-2
Electromagnetic RF fields
EN 61000-4-3
Fast transients (burst)
EN 61000-4-4
Surge
EN 61000-4-5
RF conducted interference
EN 61000-4-6
Emissions:
Emissions
EN 55011
Notes:
1. Criterion A: Normal operation within specified limits.
2. Criterion B: Temporary loss of performance from which the unit self-
recovers.
3. The module's analog input and/or output signals may deviate during
disturbance, but self-recover when disturbance is removed.
4. Power supplied from backplane via RD500 Module.

7. ENVIRONMENTAL CONDITIONS:

Operating Temperature Range: 0 to +50 °C
Storage Temperature Range: -40 to +85 °C
Operating and Storage Humidity: 85% max relative humidity, non-condensing,
from 0 to +50 °C
7ML19985MB01
Criterion B
4 kV contact discharge
8 kV air discharge
3
Criterion B
10 V/m
Criterion B
power
2 kV
signal
1 kV
Criterion B
power
1 kV L-L, 2 kV L-G
signal
1 kV
Criterion A
3 V/rms
Class A

BLOCK DIAGRAM

PORT 1
PROGRAMMING
A
PORT 2
COMMUNICATIONS
A
POWER
+
24VDC
SUPPLY
-
A
ISOLATED
PORT 3
ETHERNET
B
RD500
SITRANS RD500
Vibration According to IEC 68-2-6: Operational 10 to 150 Hz, 0.075 mm
amplitude in X, Y, Z direction 1 g.
Shock According to IEC 68-2-27: Operational 25 g's, 11 msec in 3 directions.
Altitude: Up to 2000 meters
8. CONSTRUCTION: Case body is high impact plastic. For indoor use only.
Installation Category II, Pollution Degree 2.
9. CONNECTIONS: Removable wire clamp screw terminal blocks
Wire Gage: 28-16 AWG terminal gage wire
Torque: 1.96-2.23 inch/lbs (0.22-0.25 N-m)
10. MOUNTING: Snaps on to standard DIN style top hat (T) profile mounting rails
according to EN50022 -35 x 7.5 and -35 x 15.
11. WEIGHT: 6 oz (170.1 g)
12. INPUTS:
Channels: 8 single-ended
Ranges: 0-20 mA or 4-20 mA
Effective Resolution: Full 16-bit
Programmable Scaling: ±30,000
Sample Time: 50 msec - 400 msec, depending on number of enabled inputs.
ENABLED
SCAN TIME
INPUTS
(READING RATE)
1
50 msec (20 Hz)
2
100 msec (10 Hz)
3
150 msec (6.7 Hz)
4
200 msec (5 Hz)
5
250 msec (4 Hz)
6
300 msec (3.3 Hz)
7
350 msec (2.9 Hz)
8
400 msec (2.5 Hz)
Common Mode Rejection: >110 dB, 50/60 Hz
Normal Mode Rejection: >90 dB, 50/60 Hz
Step Response Time: One scan time (to within 99% of final value)
Input Impedance: 10 
Max. Continuous Overload: 100 mA
13. ACCURACY: ±0.1% of span
14. INPUT FAULT RESPONSE: Upscale Drive, Input Fault Alarm bit set high, ALM
LED illuminates below -3 mA, and above 23 mA for 0-20 mA range; below +3
mA and above 23 mA for 4-20 mA signals.
WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT
EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR
HAZARDOUS CONDITIONS ARE NOT PRESENT.
ISOLATED
INPUTS
C
POWER
SUPPLY
Module
Page 2