Acuity Brands Aculux AX3 A WDTW Istruzioni per l'installazione - Pagina 3
Sfoglia online o scarica il pdf Istruzioni per l'installazione per Apparecchiature di illuminazione Acuity Brands Aculux AX3 A WDTW. Acuity Brands Aculux AX3 A WDTW 5. Dmx512 / rdm field
Network Installation and Setup
DMX Downlight Installation
1. Determine system layout. A DMX/RDM splitter is
required for >30 fixtures or if star configuration is
desired. See Figure 1 for an example system
layout.
2. Install DMX fixtures according to included
installation instructions.
3. Run DMX cable from eventual splitter or controller
location to first fixture or DMX/RDM splitter. Daisy-
chain cable from fixture to fixture.
4. Install included 3-position connectors on DMX
cable as shown in Figure 2 and plug into fixtures
as shown in Figure 3.
5. Ensure the termination resistor is installed into the
last luminaire in each run as shown in Figure 4.
Note: Remove and discard pre-installed termina-
tion resistor from all other fixtures.
6. Use an RDM configuration* device to discover
fixtures and set DMX start addresses.
7. Install DMX controller and connect to DMX cable.
8. Configure controller according to Tables 1-2 on
page 4.
Figure 2. DMX cable pinout for CAT5 cable.
Data out to next fixture
Data in from controller or previous fixture
Figure 3. Location of data in and out jacks
on fixture.
Product Services Phone (888) 387-2212
1300 S. Wolf Road • Des Plaines, IL 60018 • Phone 800-323-5068 • Visit us at www.acuitybrands.com/aculux
©2017 Acuity Brands Lighting, Inc.
INSTALLATION INSTRUCTIONS
Termination Resistor
(plug directly into fixture)
DMX Controller
Common
Data (-)
Data (+)
Figure 1. DMX network featuring one universe splitting into two runs of up
to 30 fixtures each.
Termination Resistor
Data in from controller or previous fixture
Figure 4. Fixtures come with pre-installed termination
resistor. The resistor should remain installed only in the
last fixture of each run.
Rev 3/17
P6160
Twisted Pair,
Shielded Cable
DMX Fixture
DMX/RDM Splitter