FirePro Sigma XT Procedura - Pagina 2

Sfoglia online o scarica il pdf Procedura per Pannello di controllo FirePro Sigma XT. FirePro Sigma XT 4. Conventional fire control panel with control unit for aerosol release, system isolation
Anche per FirePro Sigma XT: Manuale di installazione e funzionamento (14 pagine)

1. Introduction
General Information
All FirePro Fire Extinguishing Aerosol Generators use the latest generation FPC solid compound. Upon activation,
the solid compound is transformed into a rapidly expanding, highly efficient gas, based on Potassium salts. It does
not deplete oxygen levels.
maintenance required.
Ozone Depletion Potential (O.D.P.) = 0
Global Warming Potential (G.W.P.) = 0
Self Activation Temperature
FirePro Condensed Aerosols have a built-in fail-safe activation system ensures operation of the generators when
required, even if everything else fails.
When the temperature of the Aerosol units reaches 300°C the unit will activate
DO NOT Carry out any welding or grinding work in the vicinity of the aerosol units.
Handling and Storage - Condensed Aerosol Generators do not:
Disassemble the unit
Carry out any welding or grinding work in
the vicinity of the fire extinguishing
system components.
STORAGE and OPERATIONAL CONDITIONS
Temperature: –54 and +54°C
Service life: 15 years (date of manufacture appears on each generator)
Sigma_XT_Isol_1.0.Docx
The FirePro Aerosol Generators have a certified life of 15 years, with minimal
Fire Control Panel – Sigma XT
SYSTEM ISOLATION
Atmospheric Life Time (A.L.T.) = 0
Non-corrosive & Non-toxic
Exert force or impact which creates
physical or mechanical damage to the
casing.
Humidity: maximum 98% RH
Rev 1.0