Fireray FD2705R Manuale - Pagina 11
Sfoglia online o scarica il pdf Manuale per Allarme fumo Fireray FD2705R. Fireray FD2705R 12. Loop powered, analogue addressable
•
Operating Range Fireray FD2705R
•
Operating Range Fireray FD2710R
•
Supply Voltage
•
Quiescent Current (no lamp illuminated)
•
Alarm Current
•
Fault Current
•
Power Down Reset Time
•
Operating Temperature
•
Tolerance to Beam Misalignment at 35%
•
Fire Alarm Thresholds
•
Optical Wavelength
•
Head Maximum Size
•
Weight
12. Service / Application Notes.
•
For full compliance with BS5839 part 5, use 25% and 35%(default) thresholds. The threshold of 50% is
recommended for hostile and extreme environments.
•
Red LED indicates FIRE (set and cleared by panel).
•
Amber LED flashing once every 2 seconds indicates FAULT.
•
Amber LED flashing once every 10 seconds indicates normal operating mode.
13. Parts List.
•
1 off: Detector Head Assembly
•
1 off: Prism for the FD2705R
•
4 off: Prisms for the FD2710R
•
1 off: Dual Test Filter
•
Installation guide
22318.26.01
www.acornfiresecurity.com
5 to 50 metres
50 to 100 metres
10.2Vdc to 30Vdc
<4mA
<25mA
<13mA
>5 seconds
-30°C to 55°C
Detector ± 0.8°, Prism ± 5.0°
2.50dB (25%), 3.74dB (35%), 6.02dB (50%)
880nm
Width 130mm, Height 210mm, Depth 120mm
740 gm
www.acornfiresecurity.com