Operating Range Fireray FD2705R
Operating Range Fireray FD2710R
Supply Voltage
Quiescent Current (no lamp illuminated)
Alarm Current
Fault Current
Power Down Reset Time
Operating Temperature
Tolerance to Beam Misalignment at 35%
Fire Alarm Thresholds
Optical Wavelength
Head Maximum Size
Weight
12. Service / Application Notes.
For full compliance with BS5839 part 5, use 25% and 35%(default) thresholds. The threshold of 50% is
recommended for hostile and extreme environments.
Red LED indicates FIRE (set and cleared by panel).
Amber LED flashing once every 2 seconds indicates FAULT.
Amber LED flashing once every 10 seconds indicates normal operating mode.

13. Parts List.

1 off: Detector Head Assembly
1 off: Prism for the FD2705R
4 off: Prisms for the FD2710R
1 off: Dual Test Filter
Installation guide
22318.26.01
www.acornfiresecurity.com
5 to 50 metres
50 to 100 metres
10.2Vdc to 30Vdc
<4mA
<25mA
<13mA
>5 seconds
-30°C to 55°C
Detector ± 0.8°, Prism ± 5.0°
2.50dB (25%), 3.74dB (35%), 6.02dB (50%)
880nm
Width 130mm, Height 210mm, Depth 120mm
740 gm