Altronic GTI Bi-Fuel Manuale d'installazione e d'uso - Pagina 4
Sfoglia online o scarica il pdf Manuale d'installazione e d'uso per Sistemi di controllo Altronic GTI Bi-Fuel. Altronic GTI Bi-Fuel 4. Form gti+ agv5 terminal program iom 1-15
2.2 Once the setup information is correct, select OK
Once Bi-Fuel is ON and the AGV5 is powered, communication should be
established. TD and RD on the adapter will blink frequently. If TD or RD is a
solid light, there is a communication error.
3.0 Understanding the Home Screen
3.1 Connection — The Connection key allows the user to select a new computer
communication port and protocol. The Baud Rate should be set to 9600, Parity
set to None, and Packet Delay set to 100.
3.2 ResetComStats — In the event of an AGV5 power off-to-on event
(commissioning and moving to a new load point), ResetComStats can be used
to reset communication with the AGV5 without closing the terminal program or
redoing the Connection protocol.
3.3 Disconnect — The Disconnect key breaks the communication link between the
AGV5 and the computer in use.
3.4 Chart — The Chart key allows the user to display the AGV5 functions in
graphical form.
3.5 SnapShot — The SnapShot key allows the user to take a picture of the
home screen.
3.6 LogFile — LogFile can be turned on or off. LogFile records all of the data the
AGV is processing into a .CSV file.
3.7 Advanced — The Advanced key is currently for Altronic Factory Use Only. This
key allows for the change of the AGV5-xL characteristics.
3.8 Help — The Help key displays the terminal program version and date
3.9 Exit — The Exit key exits out of the program.
3.10 Control Loop Parameters — The Control Loop Parameter section of the home
screen displays the current limits the AGV5 has to operate within.
3.11 Demand (D) — The Demand (D) graph displays in percent the signal the GPN
control panel is requesting the AGV5 to achieve. This D value is the same as the
mA D value displayed on the Next screen of the GPN2020.
3.12 Sensor (S) — The Sensor (S) graph display in percent where the AGV5 is in
reference to the D value. The S value is derived from the RGP Mixer sensor. The
S value in the terminal program is not the same as the S value displayed on the
NEXT screen of the GPN2020.
3.13 Valve Positon — The Valve Positon graph displays in percent the position of the
AGV5 actuator.
3.14 Valve Drive — The Valve Drive graph displays in percent the amount of energy
being sent to the voice coil to move the valve.
GTI+ AGV5 Terminal Program IOM 1-15
All rights reserved © ALTRONIC, LLC 2015
4