Sample calculation 2
Count the horizontal lengths
Flue pipe lengths: J + L = 0,5 + 0,5=1 m
Bends: K+ M = 2 + 2 m = 4 m
Wall terminal: 1 m
Total horizontal length: 6 m
Count the vertical lengths
Flue pipe length H
Total

8 Deflector State Table

− Find the correct vertical and horizontal lengths in the table.
− In case of an "x", or if the values are outside the table, the combination is not permitted. The
value found indicates the deflector indicator ("0" meaning that the deflector is completely
open).