AKOS Uranus Left XLG Manual de instalação - Página 16

Procurar online ou descarregar pdf Manual de instalação para Lareira de interior AKOS Uranus Left XLG. AKOS Uranus Left XLG 20 páginas. Insert fireplace

Sample calculation 2
Count the horizontal lengths
Flue pipe lengths: J + L = 0,5 + 0,5=1 m
Bends: K+ M = 2 + 2 m = 4 m
Wall terminal: 1 m
Total horizontal length: 6 m
Count the vertical lengths
Flue pipe length H
Total

8 Deflector State Table

− Find the correct vertical and horizontal lengths in the table.
− In case of an "x", or if the values are outside the table, the combination is not permitted. The
value found indicates the deflector indicator ("0" meaning that the deflector is completely
open).
AKOS Sp. z o o.
ul. Bruszewska 22, 03-046 Warszawa
NIP: 5361925006; REGON 365653140
Tel: +48881697975; email: [email protected]
1 m
1m
Horizontal
0
1
2
10
13
13
10
9
13
12
10
8
13
12
10
7
11
11
9
6
10
11
9
5
9
10
8
4
8
10
8
3
7
8
7
2
7
6
5
1
6
3
2
3
4
5
6
9
6
3
7
9
5
3
7
8
6
4
6
6
5
4
5
6
6
4
5
6
4
2
4
6
4
2
3
6
5
4
2
4
3
2
1
1
0
0
0
7
8
6
5
6
4
5
4
4
3
3
3
2
2
0
2
0
0
0
X
X
X
16 <
<
<
<