DOLD RL 5898 Traduzione delle istruzioni originali
Sfoglia online o scarica il pdf Traduzione delle istruzioni originali per Strumenti di misura DOLD RL 5898. DOLD RL 5898 12. Varimeter imd insulation monitor
Monitoring Technique
VARIMETER IMD
Insulation monitor
RN 5897/240
RN 5897/240
Product Description
The insulation monitor RN 5897/240 of the VARIMETER IMD family
provides best and up to date insulation monitoring of modern IT systems
in an optimum and state of the art way fulfilling the relevant standards.
The device can be used in the most flexible way for AC, DC and AC/DC
systems. The setting of the parameters and the switching values is done
by simple and operator friendly rotational switches on front of the device.
The operating status is indicated user friendly via a multicolour LED. With
a sealable transparent cover the device is protectet against manipulation.
Circuit Diagram
VSG1
L(+)
L(-)
A1(+)
VSG2
L(+) L(-)
11
U H
PE1
PE2
12
X1 X2
11 12 14 21 22 24
PE1
Connection Terminals
Terminal designation
Signal description
A1(+), A2
Auxiliarx voltage AC or DC
Connection for measuring ciruit resp.
L(+), L(-), VSG1, VSG2
connection for coupling device
PE1, PE2
Connection for protective conductor
Control input
(combined external Test- and Reset-input
X1, X2
with additional Stop of the measuring
function)
Semiconductor output (Open Collector) with
Y1(+), Y2
PWM-signal to indicate the actual insulation
resistance
11, 12, 14
Alarm signal relay K1(1 changeover contact)
Device fault indicator relay K2
21, 22, 24
(1 changeover contact)
All Technical Data in this list relate to the state at the moment of edition. We reserve the right
for technical improvements and changes at any time.
Coupling devices
RL 5898
RP 5898
A2
Y1
(+) Y2
21
14
22
24
PE2
M12297_a
Translation
of the original instructions
Your Advantages
• Insulation monitoring according to IEC/EN 61557-8
• Suitable for DC charging stations for electric vehicles
acc. to IEC/EN 61851-23:2014/AC:2016-06
• Universal application in non-earthed AC, DC, AC/DC networks up to
AC max. 250 V or DC max. 300 V
• With connection facility of an external coupling device RL 5898 for
voltages up to AC 400 V / DC 500 V or RP 5898 for voltages up to AC
690 V / DC 1000 V
• Extended operating temperature range of - 40 ... + 70 °C
• Very fast reaction time ≤ 1 s
• Optimised insulation resistance monitoring also during
mains voltage variation
• Self-test every full operating hours
• Preventive fire and system protection
• Detection of symmetric and asymmetric insulation faults
• Universal application in non-earthed AC, DC, AC/DC networks
• Easy adjustment of response value and setting parameter via
rotational switch
• Suitable for large leakage capacitances up to 5 µF
• Monitoring also with voltage-free mains
• Measuring circuit L(+)/L(-) with broken wire detection (can be switched off)
• Protective conductor PE1/PE2 with broken wire detection
(can't be switched off)
Features
• Setting range of 2nd response value (alarm): 1 kΩ ... 500 kΩ
• 1 changeover contacts each for insulation failures alarm and
device failures
• Energized or de-energized on trip can be selected for indicator relay
• With multicolour status LED to indicate the state of operation.
• Automatic and manual device self-test
• Alarm storage selectable
• Protection against manipulation by sealable transparent cover
• External control input for combined test- / reset-button
with additional stop of the measuring function
• With semiconductor output to indicate the insulation resistance (PWM)
• 3 wide voltage input for auxiliary voltage
• Width 52.5 mm
Approvals and Markings
Canada / USA
Applications
Insulation monitoring of:
• Non-earthed AC, DC, AC/DC networks
• DC charging stations for electric vehicles
• UPS systems
• Networks with frequency inverters
• Battery networks
• Networks with direct current drives
• Hybrid and battery-powered vehicles
• Mobile generator sets
1
1)
AC/DC
RN 5897 only
1)