Cypress Suprex SPX-1300 Manuale operativo - Pagina 3
Sfoglia online o scarica il pdf Manuale operativo per Estensore Cypress Suprex SPX-1300. Cypress Suprex SPX-1300 17. Reader extender
Anche per Cypress Suprex SPX-1300: Manuale operativo (16 pagine)
2-8 to 16 VDC In
1-Ground
Diagnostic LED
8-485(+)
7-485(-)
6-+5 VDC Out
5-Prog Res 2
4-Prog Res 1
3-LED Input
2-D1/Data/F2F Out-
1-D0/CLK Out
Note: F/2F connections
support unsupervised
mode only.
2-8 to 16 VDC In
1-Ground
8-485(+)
7-485(-)
6-+5 VDC Out
5-RLY4 Input (5V)
4-RLY3 Input (5V)
3-LED Output
2-D1/Data/F2F Input
1-D0/CLK Input
DIP Switch #1 ON
Central Unit
-Service Mode
Settings
DIP Switch #1 OFF
-Run Mode
1 2 3 4 5 6 7 8
Dip switch #4 is ON
-Disable Pullup resistors
Dip switch #4 is OFF
-Enable Pullup resistors
Wiegand
Wiegand / No Filter
Strobed Rising Edge (MR-5)
Strobed Rising Edge (Dorad0 644)
Strobed Rising (Mag-Tek)
Strobed Falling Edge
Reserved
External connections and DIP Switch Settings
*
*
Switch
6 7 8
0
1
x
x = ON
2
x
3
x x
4 x
5 x
x
6 x x
7 x x x
F2F
Central Unit
Remote Unit
Remote Unit
Settings
Dip switch #4 is ON
-Enable Pullup resistors
Dip switch #4 is OFF
-Disable Pullup resistors
Wiegand / No Filter
Strobed Rising Edge (MR-5)
Strobed Rising Edge (Dorad0 644)
Strobed Rising (Mag-Tek)
Strobed Falling Edge
12-RLY4 N.O.
11-RLY4 Com
10-RLY4 N.C.
9-RLY3 N.O.
8-RLY3 Com
7-RLY3 N.C.
6-RS232 Out
5-RS232 In
4-Ground
3-Aux Out
2-Relay2 Input
1-Relay1 Input
12-RLY2 N.O.
11-RLY2 Com
10-RLY2 N.C.
9-RLY1 N.O.
8-RLY1 Com
7-RLY1 N.C.
6-RS232 Out
5-RS232 In
4-Ground
3-Aux In
2-N/C
1-N/C
DIP Switch #1 ON
-Service Mode
DIP Switch #1 OFF
-Run Mode
1 2 3 4 5 6 7 8
Switch
6 7 8
Wiegand
0
1
x
2
x
3
x x
4 x
5 x
x
6 x x
Reserved
7 x x x
F2F
x = ON