スイッチ Barksdale BLS3000のPDF 取扱説明書をオンラインで閲覧またはダウンロードできます。Barksdale BLS3000 6 ページ。 Dual level switch

7.1 Parameters
Parameter
14-segment display
SP1/SP2*
/
FH1/FH2*
/
rP1/rP2*
/
FL1/FL2*
/
EF
rES
dS1/dS2*
/
dr1/dr2*
/
Ou1/Ou2*
/
uni***
dEcP***
dLFS***
duFS***
OuA**
6
Description
Hysteresis function: switching point of solid state contact
Window function: window High solid state contact
Hysteresis function: hysteresis of solid state contact
Window function: window Low solid state contact
Extended programming functions
Reset parameters to factory settings
Switching time delay – the set contact rating must be
permanently exceeded to trigger a switching function
Switching time delay – the contact rating must be
permanently lower than the set contact rating to trigger a
switching function
Switching function of solid state contact
HNO
= hysteresis function, NO contact
HNC
= hysteresis function, NC contact
FNO
= window function, NO contact
FNC
= window function, NC contact
diA
= diagnostic function, NO contact (only Ou2)
Select unit: %, mm, cm, m, in, ft, l, Ga, m³
If the measuring range is outside the display range, unit
selection is not allowed. The parameter "uni" is not
displayed.
Decimal point display: 0.000; 00,00; 000,0 oder 0000
Display, bottom float stopper: 0... 9999
Display, top float stopper: 0... 9999
Analog output
I
= 4... 20 mA
U
= 0... 10 V
I.INV
= 20... 4 mA
U.INV
= 10... V
Parameter
14-segment display
Description
ASP**
Analog start value
AEP**
Analog end value
dPA**
Damping of analog output
ErS.A**
Error signal of analog output
values: < 3.6 or > 22 or Off
Hi
Saved value of highest level measured
Lo
Saved value of lowest level measured
COF
Offset correction (max. 10 % of measuring range)
ddis
Damping display
Fdis
Rotate display through 180°
udiS
Unit indication
Firm
Firmware version
LocK
Software lock
*
only models with 2nd switching contact
**
only models with analog output
***
no automatic conversion
If the unit and/or the display of the measured values are changed all parameters for switching
points or analog output must be checked and adjusted as required.
Error list
Parameter
14-segment display
Description
sens
Sensor defect
SC1
Short circuit, solid state contact 1
SC2
Short circuit, solid state contact 2
AOut
Open output, short circuit
OL
Sensor limit positive
UL
Sensor limit negative
KEY
Internal defect
7