- ページ 5

ネットワーク・ハードウェア Amphenol Telect 009-7001-0104BのPDF インストレーション・マニュアルをオンラインで閲覧またはダウンロードできます。Amphenol Telect 009-7001-0104B 15 ページ。 High-current demarcation panel

ALERT! Only qualified personnel may install and maintain this product. Verify that all connections meet
requirements specified in local electric codes or operating company guidelines before supplying power.

1.3 Specifications

Inputs/Outputs:
Max. fuse rating (each)
Max. total load rating of panel
Voltage range
BATT & RTN wire size
Ground wire size
Terminal stud sizes
(Input, output and earth ground)
Power dissipation
Short-circuit withstand rating
Alarms:
Alarm relay contacts
Alarm card power rating
Alarm wire size
Dimensions:
Nominal, without brackets:*
Weight:
Weight, shipping
Environment:
Operating temperature
NOTE: Wire sizes are recommended based on generally available lug sizes. Ensure wire sizes meet amperage
requirements per NEC.
High-Current
Demarcation Panel
Specification:
100A: Circuit breaker
125A: TFD holder
320A: Circuit breaker
400A: TFD holder
±20 to ±28 VDC
-40 to -60 VDC
#8 to #1 AWG recommended (see note below)
#10 to #2 AWG recommended (see note below)
1/4"-20 dual studs on 5/8" centers
Maximum lug width: 0.61-inches
17W per channel
5000A
Specification:
0.6A @ 60 VDC
1W
Solid: #26 to #22 AWG
Specification:
Width:
17.25" (43.8 cm)
Height:
1.75" (4.4 cm)
Depth:
10.4" (26.4 cm)
Specification:
~11 lbs. (~4.5 kg): 009-7001-0104B
~12 lbs. (~5 kg): 009-7001-0104B-TFD
Specification:
-5°C (23°F) to 55°C (131°F)
5
Amphenol Network Solutions
All rights reserved. 12.17.19 146161-3
509.926.6000 — amphenol-ns.com.com