- ページ 6

エアコン AirStage UTY-RHKGのPDF インストレーション・マニュアルをオンラインで閲覧またはダウンロードできます。AirStage UTY-RHKG 8 ページ。 Uty-rhk series
AirStage UTY-RHKG にも: 取扱説明書 (2 ページ), 取扱説明書 (20 ページ)

AirStage UTY-RHKG インストレーション・マニュアル

6.2. Dual remote control

2 remote controllers can be used to operate the indoor units.
The timer cannot be used on the slave units.
ADDRESS SETTING and FUNCTION SETTING cannot be used on the slave units.
The remote controller (UTB- * LA) and remote controller (UTB- * U * ,
UTB- * P * , UTB- * R * ) cannot be connected at the same time.
(1) Wiring method
(Indoor unit to remote controller)
● Type A (Terminal block)
When there are
functional earthing
cable (UTY-RHKYT)
● Type B (Connector)
Connector
Remote
controller cable
When there are
functional earthing
cable (UTY-RHKYT)
(2) Remote controller DIP Switch 1- No. 2 setting
Set the remote controller DIP switch 1- No. 2 according to the following
table.
Number of remote
controllers
DIP switch 1 - No. 2
1 (Single)
2 (Dual)
Group control and dual remote control can be used together.
When connecting 2 remote controllers, the remote controller can also be
connected together with another type of remote controller.
M
E

7. TURNING ON THE POWER

O D S
Recheck the wiring. Incorrect wiring will cause trouble.
(1) Check the remote controller wiring and DIP switch settings.
(2) Install the front case.
* When installing the front case, connect the connector to the front case
(in 5 INSTALLING THE REMOTE CONTROLLER).
(3) Check the indoor and outdoor unit wiring and PC board switch settings,
and then turn on the indoor and outdoor units.
After "
" has fl ashed on the set temperature indicator for several
second, the
mark will be displayed in the center of the remote
controller display.
*
For the wiring and PC board switch settings method, refer to the
installation manual for the indoor unit and outdoor unit.
En-5
Indoor unit
Remote
controller cable
Y1 Y2 Y3
1 2 3
1 2 3
Slave
Master
unit
unit
Remote controller
Indoor unit
Connection
1 2 3
1 2 3
Slave
Master
unit
unit
Remote controller
Master unit
Slave unit
DIP switch 1 - No. 2
OFF
OFF
ON
T
H
CAUTION

8. ADDRESS SETTING

M
Address setting method of indoor unit can be selected from 3 options (outdoor
unit, indoor unit and remote controller).
Refer to the installation manual of outdoor unit or indoor unit when set up
from the outdoor unit or the indoor unit.
"Indoor unit address" and "Refrigerant circuit address" can be set using
the remote controller.
This function can be set in all indoor units when
connected.
"Remote controller address" cannot be set in this function. Ensure to set
with the Rotary switch of PC board of the indoor unit.
When setting the address of indoor unit, refer to installation manual of
indoor unit.
When setting the address of outdoor unit automatically, refer to installation
manual of outdoor unit.
When setting the address with a remote controller, refer to installation
manual of indoor unit for setting details of indoor unit.
Switching selection of address setting mode
(1) Press the "
"
" button for more than 5 seconds simultaneously.
Then shift to Address setting mode.
(2) Press the "
the Remote controller address (Select the relevant indoor unit). Then
press "
Indoor unit address setting
(3) "Address code" indicator blinks. Then display Address code "01" by
pressing the "
-
(4) When the "Address data" blinks by pressing the "
button set the Indoor unit address data
by pressing the "
(Range of setting is 00-63.)
the remote controller is
" button, "
" button and
Address setting mode initial indicator
" button or "
" button and select
" button.
Remote controller address
Ex. When Remote controller
address "01" is selected.
" button or "
" button.
Address code
" button or "
Indoor unit address data
Ex. When Indoor unit address
data "12" is selected.
"
" button.