- ページ 11
エアコン Alen AMS09 9000 BTU AND 14.5 SEERのPDF インストレーション・マニュアルをオンラインで閲覧またはダウンロードできます。Alen AMS09 9000 BTU AND 14.5 SEER 17 ページ。 Split type room air conditioner 9000 btu and 14.5 seer/12000 btu and 13.5 seer
EvAPORATOR INSTALLATION (INDOOR)
4) Wiring
Prepare the power source for exclusive use with the air conditioner.
The supply voltage must comply with the rated voltage of the air conditioner.
Model
<12000Btu/h
>12000Btu/h
CAUTION
Perform the wiring with sufficient capacity. Installation legally requires a
short circuit isolator to be attached to prevent electrical shock.
Do not extend the power cable cord by cutting.
Power voltage should be in the range of 90% ~110% of rated voltage.
The plug of the air conditioner takes a grounding leg, so clients should
use a grounding socket so that the air conditioner can be
grounded efficiently.
5) Connecting Cables
i) Evaporator (Indoor) and Condensor (Outdoor) connecting cable should be Aw18 or more.
ii) Remove the panel and screw, then remove the window cover (for <12000Btu/h models).
Remove the panel screws covers , then remove the screws and take out the frame
(for model >12000Btu/h models)
iii) Connect cables according to their marks to terminals.
iv) Wrap those cables not connected with terminals with insula-
tion tapes, so that they will not touch any electrical components.
< 12000Btu/h models
Panel
Window Cover
Power Source
60 Hz 115V~
Frame
Panel
Screw
Plug socket and
fuse rating
32/25A
> 12000Btu/h models
Screw Cover
10
AWG (MIN)
Power Supply Cord
Connecting Cable
14
Code Wire
0.4"
1.6"
Terminal block of indoor unit
Frame
18
To outdoor
unit