CONDENSOR INSTALLATION (OUTDOOR)

3) Refrigerant Piping Connection

i) Flaring
Cut a pipe with a pipe cutter
Insert a flare nut into a pipe and flare the pipe
Excessive torque can break the flare nut and cause a leakage of refrigerant.
* Ensure the refrigerant pipe is firmly attached before running the compressor.
Outer Diameter (inches)
O 1/4
O 3/8
O 1/2

4) Wiring Connection

Condensor (Outdoor) Unit
Terminal block
Over 1.7"
Cover Control
Power supply cord
Special Branch Circuit Breaker
(Fuse/Breaker capacity: 20A)
A (inches)
Max.
Min.
0.5
0.028
0.6
0.04
0.7
0.04
Conduit panel
Connecting
cable
Power
supply
cord
Power supply
115V - 60Hz
ii) Tightening Connection
Align pipes to be connected.
Sufficiently tighten the flare nut with
fingers, and then tighten it with a
spanner and torque wrench as shown.
CAUTION
Outer Diameter
O 1/4
O 3/8
O 1/2
i) Remove the cover control from the unit by
loosening 3 screws.
ii) Dismount caps on the conduit panel.
iii) Temporarily mount the conduit tubes
(not included) on the conduit panel.
iv) Properly connect both the power supply
and low voltage lines to the corresponding
terminals on the terminal block.
v) Ground the unit in accordance with local
codes.
vi) Be sure to size each wire allowing several
inches longer than the required length for
wiring.
vii) Use lock nuts to secure the conduit tubes.
Note: To prevent wires from loosen-
ing or leaving the Cord Clamp, please
select proper cord diameter to fill the
holes on the cord clamp
12
Additional Tightening
Tightening Torque
(N. inches)
torque (N. inches)
11.57 ft lbs
14.45 ft lbs
(160kgf.cm)
200kgf.cm)
21.7 ft lbs
25.30 ft lbs
(300kgf.cm)
(350kgf.cm)
36.14 ft lbs
39.75 ft lbs
(500kgf.cm)
(550kgf.cm)