- ページ 11
ボイラー Drazice OKC 250 NTRR/SOLのPDF 操作および設置マニュアルをオンラインで閲覧またはダウンロードできます。Drazice OKC 250 NTRR/SOL 17 ページ。 For solar systems
Drazice OKC 250 NTRR/SOL にも: 操作および設置マニュアル (12 ページ)
2.2.2 EXAMPLE OF CONNECTING A TANK WITH SOLAR COLLECTORS AND A GAS BOILER
Connecting a tank to a boiler heating circuit:
The tank is placed on the ground, next to the heating source, or in its vicinity. The heating circuit is connected
to marked inlets and outlets of the tank's heater exchanger; deaeration valve is mounted in the highest place.
It is necessary to install a filter into the circuit in order to protect pumps, three-way valve, backflow flaps and
the exchanger from sedimentation. It is recommended to flush the heating circuit before the assembly.
All wiring connections must be properly insulated from heat.
If the system works with priority heating of HUW using a three-way valve, always follow the installation
instructions of the three-way valve's manufacturer.
Figure 3
The output hot water pipe on heaters with a volume of more than 200 litres is fitted with another DN 20
safety valve and opening pressure identical to the maximum operating pressure of the heater tank. This
safety valve does not replace the safety valve on the cold water inlet. No shut-off valve, non-return valve or
filter may be placed between the safety valve and the heater.
- 11 -