- ページ 4

バーナー Anderson ANM77のPDF 操作マニュアルをオンラインで閲覧またはダウンロードできます。Anderson ANM77 14 ページ。

combustion chamber is purged. If it is ignited at a low temperature, it needs to be replaced
with 5 times the volume of the combustion chamber to avoid explosion.
However, it is not necessary to purge when the temperature is higher than 750℃. Air pipe
or gas pipe connected with burner should be tight enough with no leakage, also the
periodically check air or fuel nozzles of the burners to prevent to be blocked by dust, slag
or other materials.
ATTENTION: DANGER OF BEEN BURNT
When burner in operation, combustion is severe, so the burner must be fixed. Hoses or
cables in area of the combustion system must be suitable for high temperature, to prevent
high temperature failure or cause safety accidents. Burners should be periodically
inspected and cleaned. Copper wire brush may be used, if necessary, to clean burner head.
The burner system should be checked twice a year for safety operation.
Burner commissioning shall take care of ignition position, minimum and maximum output
position. Following interlocks will cause emergency stop, including gas low pressure, high
pressure or low combustion air pressure, as well as emergency stop is trigged, the main
power is out, UV signal failure or kiln safety conditions (such as high temperature limit, flue
system opening, etc.) will cause the burner lockout. Users need to know the maintenance
interval recommended by the manufacturer and the interval specified by national laws,
whichever is shorter.

4. Fuel Information

Following table shows combustion fuel characters of natural gas, safety rules must be
obeyed when operation carried out.
Fuel
Low Calorific value
Composition
Reference conditions

5. ANM77 Series Burner Description

ANM77 series Burner is a patented product of Anderson Thermal Solutions (Suzhou) Co.,
Ltd. This series of linear burners adopts a modular structure design concept and can be
configured to match shapes according to site requirements.
It is an ideal choice for generating large amount of clean and hot air. Applications include
ovens, dryers, flue gas incinerators and similar industrial equipment, and are widely used
in heating industries such as gypsum board. This type of burner is designed based on the
Anderson Thermal Soluions(Suzhou)Co. Ltd.
Anderson Thermal Solutions – ANM77 Burner Operation Manual
Natural gas
35,900 [kJ/m
1,013.25 mbar, 0°C
2
3
]
>98% CH
4