- ページ 13
バッテリーチャージャー Compact C3048のPDF ユーザー・インストール・マニュアルをオンラインで閲覧またはダウンロードできます。Compact C3048 14 ページ。 Sinewave inverter, battery charger
Studer Solartechnik
Programming the Auxiliary Relay Contacts
The Auxiliary Relay Contacts can be programmed to switch due to a wide variety of fault conditions or
normal operating modes. (Any function that has a LED on the control panel can be programmed). One
or more operating conditions can be programmed, the first of which to occur will operate the relay.
Firstly press button 21 for a minimum of 2
seconds to enter the Auxiliary Contacts
programming mode. The 'Program' LED 4
will illuminate. Use button 20 to select the
desired condition you wish the Aux. contacts
to be activated by. Use button 19 to select or
deselect that option. An illuminated LED
indicates that condition will activate the
contacts. Using this same method, step
through as many conditions as required to
activate the contacts. After program-
ming wait 10 seconds and the new
settings will be stored. The COMPACT is
usupplied with the following conditions
activating the Aux. Contacts:
1. Over temperature
2. Overload
3. Battery Over-voltage or Under-voltage
4. If the COMPACT has been turned OFF
manually or with a fault.
Example 1:
Activate the auxiliary contacts only when in the Over Temp condition
Press button 21 for a minimum of 2 seconds to enter the Auxiliary Contacts programming mode. The
'Program' LED 4 will illuminate. Use button 20 to select the Overload condition. Use button 19 to
illuminate the Overload LED , if it is not already illuminated. Step through the rest of the options using
button 20. If any of the other options show illuminated LEDs, press button 19 to deselect them (switch
off the LED). Once finished wait 10 seconds and the 'Program' LED will go off and the new settings will
be stored.
Example 2:
Auxiliary Contacts as a generator starter.
When in the programming mode for the Aux. Contacts, the battery condition LEDs 15-18 can be used to
determine when to switch On and Off an external generator. i.e. when LED 18 illuminates the battery
capacity is low and the generator should be started. When LED 15 is illuminated the batteries are almost
fully charged and the generator can be switched off.
Manually operating the Aux. Contacts
The Aux. Contacts can be operated at any time by pressing the 'Aux. Contacts' button 21. LED 6
'Contact Manual' illuminates and LED 5 'Contact active' illuminates. By pushing button 21 again the
Contact is deactivated. Pushing button 21 a third time takes you back to the automatic mode.
Sinewave Inverter, Battery Charger
LED functions in voltage
programming mode
Program
4
21
- 13 -
20
14
15
16
17
18
19
LED 10 Over Temp
LED 11 Overload
LED 12 Batt Low/High
LED 13 Off