- ページ 5

産業機器 DuctSox SkeleCore Pull-Tight CableのPDF インストレーション・マニュアルをオンラインで閲覧またはダウンロードできます。DuctSox SkeleCore Pull-Tight Cable 16 ページ。

DuctSox
SkeleCore Pull-Tight Cable
®
Installation Manual
The following details are used for Galvanized Cable styles.
1. Eyebolts must be fastened to the structure of the building (including knee braces) by
others. They must be fastened in correct locations according to suspension style (Shown in
each suspension style's section).
2. Hook Gripple
Turnbuckles to the installed eyebolts.
®
3. Insert cable into the plastic end of the Gripple
Turnbuckle and push/pull it through
®
the opening on the side of the Gripple
Turnbuckle.
®
Note: To release the cable hold in the plastic button and slide the turnbuckle.
To lock the button twist the plastic until tight.
4. Tighten the cable to 100 lb (445 Newtons) tension by pulling the cable tight and then
twisting the turnbuckles. Clip extra cable when finished, leaving about 3 in (76 mm) of
cable extending through the side the Gripple Turnbuckle.
Publication: AMEN00417 2021-02-22
5