- ページ 7
産業機器 DuctSox SkeleCore Pull-Tight CableのPDF インストレーション・マニュアルをオンラインで閲覧またはダウンロードできます。DuctSox SkeleCore Pull-Tight Cable 16 ページ。
DuctSox
SkeleCore Pull-Tight Cable
®
Installation Manual
Step 3
Determine placement of cable (both cable path and elevation). The cable
1.5 in (38 mm)
must be mounted 1.5 in (38 mm) above the 12:00 location of the DuctSox.
Intermediate Cable supports are spaced no more than 12.5 ft (3810 mm).
T's
There should be roughly 12 in (305 mm) from sidewall of DuctSox to the
closest edge of any knee-bracing. Structure too close to the main run may
cause premature failure due to abrasion from the structure.
NOTE: Offset distance of branch knee-brace from main trunk is
approximately half of the main trunk diameter plus 12 in (305 mm).
12 in (305 mm)
12 in (305 mm)
Elbows
Extended straps on heels of elbows are provided for support to cable suspension (Figure A). Vertical elbows are also
supported by extended straps (Figure B).
Figure A
Figure B
Publication: AMEN00417 2021-02-22
7