Option 38 - Relay State on Low Battery Detect
(Battery powered versions only)
This establishes the position that the relay is driven to
when the unit shuts down due to low battery state.
Press + until Option 38 is displayed, use V or Λ to
select required setting. This option is only possible on
GB
battery versions.
0 = Output OFF (Factory setting)
1 = Output ON
Option 40 - Number of Events per Day
This sets the thermostat to operate with either 2, 4 or 6
switching events per day or to run in stat mode. Press
+ until Option 40 is displayed, use V or Λ to select
required setting.
1 = Stat
(Manual operation - no programming function)
2 = 2 Events per day
4 = 4 Events per day
6 = 6 Events per day (Factory setting)
Option 41 - Operating Mode
(7 Day, 5/2 Day or 24 Hour)
This sets the thermostat to operate using either 7 day,
5/2 day or 24 hour mode. Press + until Option 41 is
displayed, use V or Λ to select required setting. This
option is not possible if the thermostat is set to STAT
in option 40.
7 = 7 Day (Factory Setting)
5-2 = 5+2 Day (or A-B if A days is set in option 1)
24 = 24 Hour