CHIMNEY REQUIREMENTS
WOOD BURNING
For minimum chimney sizes and types see table below. Certified equivalents tested and listed to UL Test Procedure
103, and ULC S604 rated to 1700°F or 2100°F may also be used if minimum chimney diameter is adhered to.
12" ID/15" OD Air-Cooled (FMI or Vanguard 12DM, Lennox FTF13, Simpson Durachimney II)
PFM36
12" ID/15" OD Air-Cooled (FMI or Vanguard 12DM, Lennox FTF13, Simpson Durachimney II)
PFM42
PFM48
PFM60
GAS LOG CONVERSIONS WITH TYPE B-VENT CHIMNEY
When the fireplace is to be converted to gas burning, and solid fuels are never to be burned, then B-Vent type
chimney may be used per the National Fuel Gas Code restrictions (see TABLE 2 below). B-Vent inside diameter
should be a minimum, but not limited to, 8".
WARNING! B-Vent Chimney should never be used when solid fuels are to be burned!
FOLLOW THE INSTALLATION MANUAL PROVIDED BY THE GAS LOG MANUFACTURER
These tables outline allowable B-
Vent diameters for a given BTU
of a natural gas log conversion
set at a defined chimney height
and lateral run. Outlined values
are if two 45 degree elbows are
used.
If four 45 degree elbows are
used, reduce maximum BTU by
10%
If two 90 degree elbows are
used, reduce maximum BTU by
10%.
TABLE 2.
national fuel gas code allowable B-Vent sizes per BTU
Chimney Type and Sizes
12"ID/14" OD Class "A" (ICC 12"RIS, Duratech 12")
12"ID/14" OD Class "A" (ICC 12"RIS, Duratech 12")
14" Air-Cooled (Simpson Durachimney II)
14"ID Class "A" (ICC 14"RIS, Duratech 14")
16" Air-Cooled (Simpson Durachimney II)
16"ID Class "A" (ICC 16"RIS, Duratech 16")
Vent Diameter
Height
Lateral
MAXIMUM BTU of Gas
ft
ft
Log System in Thousands
10
0
2
5
10
15
0
2
5
10
15
20
0
5
10
15
20
8" B-Vent
Height
ft
405
30
319
311
297
472
50
372
362
347
335
517
100
414
398
384
369
7
Minimum
I.D. Chase
Clearance
2"
19"x19"
2"
19"x19"
2"
20"x20"
2"
22"x22"
TABLE 1.
chimney requirements
Vent Diameter
8" B-Vent
Lateral
MAXIMUM BTU of Gas Log
ft
System in Thousands
0
585
5
471
10
456
20
425
0
637
5
544
10
530
20
500
30
469
0
693
5
622
10
611
20
599
30
564
50
517
Size