SCREEN
LAMP TEST
If the arrow-up button is held pressed for 3 seconds the Lamp
Test mode will start.
In this mode all lights will turn on. After 3 seconds or if the
Menu button is pressed the device resumes normal operation.
PROGRAM PARAMETER LIST
DESCRIPTION
CHARGE TIMER ()
This parameter adjusts the charge time for
the battery set. The format is
Hours:Minutes.
LOW BATTERY VOLTAGE LIMIT ()
This is the battery voltage where the
genset starts.
MAINS WAITING TIMER ()
This is the period between the mains is
restored and the genset stops. The format
is Minute:Second
MAINS VOLTAGE LOW LIMIT ()
Below this limit, the mains phase voltage is
supposed to fail.
MAINS VOLTAGE HIGH LIMIT ()
Above this limit, the mains voltage is
supposed to fail.
-7-
V-1.1
(24.03.2015)
MIN
MAX
0
18hour
9V
48V
0
30min
70V
270V
100V
300V