DKG-190 User Manual
SCREEN
LAMP TEST
If the arrow-up button is held pressed for 3 seconds the Lamp
Test mode will start.
In this mode all lights will turn on. After 3 seconds or if the
Menu button is pressed the device resumes normal operation.
PROGRAM PARAMETER LIST
DESCRIPTION
CHARGE TIMER ()
This parameter adjusts the charge time for
the battery set. The format is
Hours:Minutes.
LOW BATTERY VOLTAGE LIMIT ()
This is the battery voltage where the
genset starts.
MAINS WAITING TIMER ()
This is the period between the mains is
restored and the genset stops. The format
is Minute:Second
MAINS VOLTAGE LOW LIMIT ()
Below this limit, the mains phase voltage is
supposed to fail.
MAINS VOLTAGE HIGH LIMIT ()
Above this limit, the mains voltage is
supposed to fail.
-7-
V-1.1
(24.03.2015)
MIN
MAX
0
18hour
9V
48V
0
30min
70V
270V
100V
300V