- ページ 3

ドア開閉システム Cookson FDO-A10EのPDF オーナーズマニュアルをオンラインで閲覧またはダウンロードできます。Cookson FDO-A10E 19 ページ。 Industrial duty fire door operator

The FDO-A10E medium duty motor operator is designed for use only with Service Counter Fire
Door models FD1O-1M and FD10-2M as manufactured by the Cookson Company Inc.
Door sizes range from 4'-0" x 4'-0" to 14' max opening width to 9'-0" max clear opening height.
(Smaller doors may be available with Engineering approval on a case-by-case basis.

GENERAL DESCRIPTION:

The UL-325 compliant Fire Door Operator, FDO-A10, is an integrated fire door control system. It is
designed to interface with Normally Closed (NC) or Normally Open (NO) dry contacts from the alarm
system or initiating device to control the operation of a fire door. The control station will operate
with either standard B2 or C2 wiring. This operator will require the proper self diagnostic entrapment
protection device(s) to be connected and working properly to allow B2 (Momentary Pressure on the
Close button) to close the door.
THIS OPERATOR IS NOT A FIRE ALARM SYSTEM.
IT CAN NOT DETECT A FIRE CONDITION
1. FDO-A10 MODEL: (With entrapment detection devices installed and working properly.
1.1 UNIT HAS AC POWER & NO ALARM CONDITION:
The B2 control station is used to operate the door
electrically.
Activation of the sensing edge or Photo eyes while door is closing
will cause it to reverse to full open limit.
1.2 ALARM CONDITION W/ AC POWER:
Door begins closure after a preset time delay of 0 or 10 seconds (Set at 10 seconds
on basic unit, 0 second selectable if unit is equipped with expansion module).
If obstruction is encountered by entrapement protection device(s), door will reverse to
OPEN position and attempt closure again. The door will cycle up to 3 times before
resting on the obstruction. If the obstruction is removed, the door will continue to the
fully CLOSED position.
The OPEN button will raise the door to the fully open position, and after a 10 second
delay will begin closing again. This will work until the third attempt to close has been
used, and then all OPEN functions will be disabled until the alarm has been reset.
Note: All OPEN functions initiated by the photo eyes or sensing edge can be disabled
in the event of an active alarm condition, if the unit is equipped with the expansion module.
When this feature is selected, and an obstruction is detected by the entrapement
protection device(s), the door will rest on the obstruction. If the obstruction is later
removed, the door will travel to the fully CLOSED position.
9001(7) ECN 1057 4/10/010

THEORY OF OPERATION

NOTICE
WARNING
TO REDUCE THE RISK OF INJURY TO PERSONS,
USE THIS OPERATOR ONLY WITH ROLLING DOORS.
3