モニター Bender NGRM700のPDF クイック・スタート・マニュアルをオンラインで閲覧またはダウンロードできます。Bender NGRM700 8 ページ。 Neutral grounding resistor monitor (ngr)
Bender NGRM700 にも: クイック・スタート・マニュアル (8 ページ), マニュアル (8 ページ), クイック・スタート・マニュアル (8 ページ)

Quickstart
NGRM700
EN
Neutral Grounding Resistor Monitor

Intended use

The NGRM700 is only intended for use in high-resistance earthed sys-
tems. In these systems, the NGRM700 monitors
the current through the NGR,
 
the voltage between the star point of the transformer and earth
 
(voltage drop across the NGR),
the condition of the neutral grounding resistor (NGR),
 
line-to-line and line-to-earth voltages.
 
This quick-start guide does not replace the operating manual of the device.
Download:
www.bender.de/manuals

Safety instructions

Risk of electrocution due to electric shock!
Touching live parts of the system carries the risk of:
 
DANGER
 
 
Before installing and connecting the device, make sure that the installation has
been de-energised. Observe the rules for working on electrical installations.
Removing FP200-NGRM
PH 1
Connection X1
I1
I2
I3
A
B
M+
Q2
Q1
+
NGRM700_D00292_02_Q_XXEN/06.2018
An electric shock
Damage to the electrical installation
Destruction of the device
1
X1
ET H
R
I1
Pulser IN
I2
Reset IN
I3
Test IN
A
Modbus RTU (A)
B
Modbus RTU (B)
Ground
M+
Analogue output
Q2
Open Collector: Pulser OUT
Q1
Open Collector: System health
+
Output for supply of external relays (+24 V, max. 100 mA)
X1
ET H
R
OFF
ON
RJ45:
Remote
max. 5 m
Switch
RJ45:
Ethernet
1