TROUBLESHOOTING

Troubleshooting Guide 1
Engine Will Not Start
Checklist - After You Stop Cranking
Indicates the Overspeed limit was exceeded during
starting. Recheck Flywheel Teeth, Overspeed, and
N
Speed settings. Cycling the power on the IGC will
remove the Overspeed Fault Condition.
Restarting.
Y
IGC is in SETUP Mode. Press and hold the RUN
Button to exit Setup mode. The Fault LED should
turn off. If it doesn't, that means the Overspeed limit
was exceeded during starting.
Teeth, Overspeed, and Speed settings. Cycling the
Y
power on the IGC will remove the Overspeed Fault
Condition. Try Restarting.
N
N
Is the battery (+) connected to Terminals A & C? Is
Battery (-) connected to Terminal B? Verify polarity.
Y
Connect
Battery
N
Y
13
Recheck Flywheel
N
Measure
Voltage
Terminals A(+) and B(-) to
verify sufficient Voltage (12V
or 24V). Cycle Power. If still
no
LED's turn on,
controller
needs
replaced.
Try
Y
across
then
to