- ページ 10
コントローラー AGS Merlin 1000S+のPDF インストレーション オペレーション&メンテナンスをオンラインで閲覧またはダウンロードできます。AGS Merlin 1000S+ 12 ページ。 Gas and electric isolation controller
AGS Merlin 1000S+ にも: ユーザーマニュアル (12 ページ)
Installation & Operation Manual
Operation
Initial Power Up
All services can be turned on or off within 10 seconds only of the key switch being turned on. After 10 seconds, all utility
buttons will be disabled. The user must turn the key off and back on to adjust any services.
Turn the key switch to on position. Gas & Electric LEDs will flash for 10 seconds. Press relevant service
button to turn required utility on.
LED Indicators
•
Gas
When the key switch is turned on, the system will check the installation for gas leaks.
If gas proving is successful, the LED will illuminate.
•
Electric
When electric service is turned on, the Electric LED will illuminate.
ON = Electric on / FLASHING = Electric Off, Electric button enabled / OFF = Electric Off, Electric button disabled.
•
Testing
This LED will illuminate GREEN for approximately 30 seconds when the panel is checking the integrity of
the gas installation upon start up.
•
Test Fail
Under normal working conditions this LED is off. When the panel detects a gas leak on start-up, the LED
will illuminate AMBER. Gas valve will remain closed.
•
Pressure Low
Under normal working conditions the LED is off. The LED will illuminate AMBER when pressure of the
gas supply drops below 0.17psi for 10 secs. The gas valve will close.
•
Timeout
Under normal working conditions this LED is off. This LED will illuminate AMBER when auto-shut down
has occurred.
OFF = OK / ON = Auto-shut down activated
•
EM Stop
If an emergency shut off button (either remote or on the panel) is pressed, the LED will illuminate
AMBER and the gas will be turned off and the fans switch (if a fan switch is connected). The EM Stop
button must be reset before restarting the system. The emergency shut off button(s) will cut off the gas
supply, electrics, and fans (if connected) when activated.
•
CO2/ Gas Detected
Under normal working conditions this LED is off. If the external Merlin detector connected detects gas
this will show RED, and the gas valve will turn off.
•
CO
High
2
Under normal working conditions this LED is off.
If the concentration of CO2 in the air is at alarm level (relevant detector required), the LED will show
RED, and the gas valve will close.
Rev: 13
08-22
ON = Gas On / OFF = Gas Off
ON = proving the gas line, do NOT operate any appliances.
OFF = OK / ON = gas proving failed.
OFF = OK / ON = Gas detected.
OFF = OK / ON = the concentration of CO2 is at alarm level.
OFF = OK / ON = gas supply pressure low.
OFF = OK / ON = Emergency Shut-Off button activated.
Merlin 1000S+
10