INSTALLATION

Planning

Our detectors should be installed in areas at risk of gas leaks e.g. over boilers, valves or meters.
Take in to account the design of the air flow patterns within the zone area.
Detectors should be installed in the correct orientation, as recommended by the manufacturer,
and ease of access should be accounted for to allow for any bump tests, recalibration and
other forms of maintenance.
Areas to avoid
Avoid conditions of any other environmental factors that could potentially impede the
accuracy and operation of the detectors such as; condensation; vibration; temperature,
pressure, the presence of other gases, electromagnetic interference and draft zones.
Area of coverage
Consider the coverage required and function of the area. Emphasis should be placed on airflow
patterns and correct placement, not perceived detecting ranges. The target gas will only be
identified when contact is made with the sensing element itself.
Maximum Gas Detectors Per Zone
Merlin 'S' panel range
Merlin 'GDP' panel range
Merlin 'GDP-X' panel range

Typical Location and Positioning

Locations for detectors will vary based on the intended application and target gas, they should
be located near identified sources of a potential gas leaks/ pockets where hazardous gas could
quickly accumulate and areas of identified consequential risk.
The composition of the target gas and its density relative to air are used as the basis for the
recommended height of sensors. Generally, the installation height of a sensor for a heavy gas
(such as propane) would be close to the lowest point in the area, and for a light gas (such as
methane) would be close to the highest point in the area.
These recommended heights may vary based on air flow and temperature conditions in
addition to the proposed application and location – this is particularly apparent with oxygen
depletion sensors, and the target gas that they are used for.
Target Gas
Natural Gas/Methane (NG/CH
Liquid Petroleum Gas (LPG)
Carbon Monoxide (CO)
Hydrogen (H)
Oxygen (O
)
2
* If you are installing and monitoring Oxygen depletion – consider the density of gas for its
application and position the detector accordingly i.e. ground level for high density gases.
AGSDETTFT-IOM Iss: 5 06-20
1
3
4
Typical Detector Position
)
High Level - 1ft from ceiling
4
Low Level - 1ft from ground level
Breathing Zone - 5ft 6" from ground level
High Level - 1ft from ceiling
*Breathing Zone - 3 - 5ft from ground level
Multiple detectors may be required to
adequately protect property and persons.
Merlin Gas Detector TFT
3