- ページ 14

チラー Gree HLR10Pd/Na-KのPDF ユニット設置マニュアルをオンラインで閲覧またはダウンロードできます。Gree HLR10Pd/Na-K 18 ページ。 Mini chiller

Gree HLR10Pd/Na-K ユニット設置マニュアル
Unit Installation

4.12 Wiring of the Remote Air Temperature Sensor

NO
Electric box
Notes:
Distance between the monobloc unit and the remote air temperature senor should be less than 15
meters due to length of the connection cable of remote air temperature sensor;
Height from floor is approximately 1.5 meters;
Remote air temperature sensor can not be located where the area may be hidden when door is open;
Remote air temperature sensor can not be located where external thermal influence may be applied;
Remote air temperature sensor should be installed where space heating is mainly applied;
After the remote air temperature sensor is installed, it should be set to "With" through the wired
controller so as to set the remote air temperature to the control point.

4.13 Wiring of the Thermostat

Installation of the thermostat is very similar to that of the remote air temperature sensor.
Front side
Remote Air Temperature Sensor
NO
Back side
YES
1.5 Meters
Remote Air Environment
Temp sensor
15K
CN1
2
12
NO
NO
Doors