To assemble the DC plug connectors, proceed as detailed below. Ensure the plug connectors have
the correct polarity. The whole connector will include the male side and female side as showed
below.
Assembly Instructions:
1. Adjust the striper stopper and put the cable in corresponding notch to strip the length of
12mm. Please see below figures.
2. Insert striped cable into contact barrel and insure all conductor strands are captured in the
contact barrel. Please see below figures.
3. Compress them together with the crimping pliers. Please see below figures.
4. Insert contact cable assembly into back of male and female connector. A "click" should be
heard or felt when the contact cable assembly is seated correctly. Then turn the cap to the
coupler. Please see below figures.
5.3.3 Connecting the PV Generator (DC)
DANGER!
Danger to life due to high voltages in the inverter.
• Before connecting the PV generator, ensure that the AC&DC circuit breaker is switched off and
that it cannot be reactivated.