Assign sensors to slots

Any sensor to be used by the Modbus interface must first be allocated to specific location (slot)
within the bridge. Once allocated, this sensor readings are guaranteed to always be in a fixed
register address.
Readings from sensors that were not assigned to a slot, will not be provided via the Modbus
interface (but will continue to be sent to PowerRadar if 'Connect to PowerRadar' is set in the
connection configuration page).
Assign a sensor to a slot
1. Navigate to the 'Sensors' tab
2. Choose an empty slot and press the '+' icon
3. In the popup dialog:
a. Type the sensor serial number
b. Type the calibration key if you have it or click 'Get calibration key' to have it
automatically retrieved and inserted.
4. The sensor is now assigned to the slot. New readings will be shown in this screen and
made available via the Modbus TCP interface.
Figure 7 The Sensors Tab
Figure 8 Add Sensor Pop-up