3.2.2 Package
POWER
RUN
FAULT
Wall-mounted
Inverter×1
Bracket×1
Terminal×1*
Screw×4
*There is 1 pair of DC connectors in NS Series 1-3KW. and 2 pairs of DC connectors in NS Series 3.6-5KW and D-NS Series 3-5KW;
*AC connector is applied to both NS Series 3.6-5KW and D-NS Series 3-5KW;
*AC terminal is applied to NS Series 1-3KW;
*There are 2 terminals in Australian model。

3.3 Inverter Installation

3.3.1 Selecting the installation location
The following must be considered when selecting the best location for an inverter:
●The mount and installation method must be appropriate for the inverter's weight and dimensions.
●The location must be well ventilated and sheltered from direct sunlight.
●The inverter must be installed vertical or with a backward tilt less than 15°. No sideways tilt is allowed. The connection
area must point downwards. Refer to Figure 3.3.1-1.
03
1. PV input terminals
2. DC Switch (Optional)
3. RS-485 port or USB port
4. Wi-Fi antenna port (Optional)
5.
Anti Reverse Current Module
(Optional)
6. AC output terminal
7. LCD display
8
8. Indicator lights
POWER
RUN
9
9. Button
FAULT
Figure 3.2.1-2
or
&
AC PlugX1*
AC Terminal×4*
DC PlugX2pair*
Quick
User
Installation
manual
Guide
Wi-Fi Connection
User Manual×1
Quick Installation
Expansion Bolts×5
(Wi-Fi model only)
Guide×1
To allow dissipation of heat, and for convenience of dismantling, clearances around the inverter must be at least:
200mm
Wi-Fi
Connection
Guide
Antenna×1
Guide×1
3.3.2 Mounting Procedure
(1) Use the wall-mounted bracket as a template and drill holes in the wall, 10 mm in diameter and 80 mm deep. NS 1kW~3kW
referred to Figure 3.3.2-1, NS 3.6kW~5kW & D-NS 3kW~5kW referred to Figure 3.3.2-2.
(2) Fix the wall mounting bracket on the wall using the expansion bolts in the accessories bag.
(3) Hold the inverter by the side groove as Figure 3.3.2-3.
(4) Install the inverter on the wall-mounted bracket. NS 1kW~3kW referred to Figure 3.3.2-4, 3.3.2-5. NS 3.6kW~5kW & D-NS
3kW~5kW referred to Figure 3.3.2-6, Figure 3.3.2-7.
125mm
Max
15°
Figure 3.3.1-1
300mm
200mm
300mm
POWER
RUN
FAULT
500mm
Figure 3.3.1-2
250mm
125mm
250mm
260mm
265mm
Figure 3.3.2-1
Figure 3.3.2-2
Upward ----------300mm
Downward--------500mm
Front-------------300mm
Both sides---------200mm
Figure 3.3.2-3