4.1 PROGRAMMING WITH MECHANICAL LIMIT SWITCH
ATTENTION: to let the safeties work, these must be connected before starting the control unit setup.
Setup process - Mechanical limits standard
Set DIP10 in OFF position for selecting mechanical limits and DIP1 and DIP2 to OFF position for deadman operation.
Standard control for mechanical limits are for PNE edge type (3-4 terminals on X5) and no photo connected.
1
ATTENTION: Switching DIP10 to ON position and back to OFF will reset to mechanical standard with ONLY PNE edge
type.
Press OPEN or CLOSE to the desired close and open limit position and adjust cam until the limit is correct.
2
Note: if door is moving in the wrong direction the 2 phases on the mains connection must be interchanged.
Limits are now adjusted.
3
Check that the safety edge is working (if mounted).
Setting process - Mechanical limits with other safety connected
ATTENTION: additional safeties as OSE (connected to X5 5-6-7) or photocell (connected to X6 9-10-11-12)
will be active only after the setting process
4
Make setup process 1 and 2 and move the door away from close limit.
Connect the requested safeties.
5
Activate setting by pressing OPEN+STOP for about 10 sec then release. The red LED FAIL (PCB) start with 2 short flashes
6
Press STOP to stop setting the edge type and photo. Yellow LED SPEED/SER confirming with 1 sec
Limits are now adjusted and edge type and photo circuit are memorised. Check that the safety functions are working as
7
expected.
ATTENTION: moving DIP10 to ON position and back to OFF will reset to mechanical standard with ONLY PNE edge type.
4.2 LED GUIDANCE
Yellow LED CONF./SER. (PCB)
Service needed (open
Fixed light
counts reached)
Confirming learning
1 sec. flash
process
Red LED FAIL (PCB)
If Photo or Edge is activated
Fixed light
when CLOSE pushbutton is
activated
1 long flash
Auto close learning active
Limits, edge and photo not
2 short flashes
learned
Force control (speed) not
2 long flashes
learned
3 long flashes
Door stopped by force control
4 long flashes
Door stopped by runtime
Door stopped by force control
5 long flashes
wear
6 long flashes
Tacho failure – pulses missing
Fail state PNE edge monito-
Continues long
ring. Check impuls by floor
flashes
missing.
Yellow LED STOP (PCB)
Stop activated or both limits
Fixed light
are active
1 long flash
Safety chain activated
2 long flashes
Photo – safety test failed.
Safety edge – safety test
3 long flashes
failed.
Stop circuit – safety test
4 long flashes
failed.
Safety chain – safety test
5 long flashes
failed
EEPROM failure. Elec.
6 long flashes
Counter or position counter by
force control
EEPROM failure. Powerup
7 long flashes
failure
8 long flashes
Welded contactor fail
9 long flashes
Internal watchdog timeout.
10 long flashes Main processor crystal fail
Green LED POWER (PCB)
The controller is powered
Fixed light
Red LED CIRCUIT ERROR (PCB)
PCB circuit error fail
Fixed light
9