- ページ 8

屋外暖炉 Empire OLI24NのPDF 取付説明書および取扱説明書をオンラインで閲覧またはダウンロードできます。Empire OLI24N 20 ページ。 Ventless decorative appliance intermittent ignition

Empire OLI24N 取付説明書および取扱説明書
2. Ventilation opening(s) shall be provided at floor
level and shall have a total free area of not less
than 1/2 square inch per pound (3.2 sq. cm/kg) of
stored fuel capacity and not less than a total free
area of 10 square inches (64.5 sq. cm). If ventila-
tion openings at floor level are in a side alll, there
shall be at least two openings. The bottom of the
openings shall be at floor level and the upper edge
no more than 5 inches (127 mm) above the floor.
The openings shall be equally sized, spaced at 180
degrees (3.14 rad) and unobstructed.
3.
Every opening shall have minimum dimensions so
as to permit the entrance of a 1/8 inch (3.2 mm)
diameter rod.
This series is design certified in accordance with American National
Standard/CSA Standard Z21.97 Outdoor Fireplace, respectively, by
the Canadian Standards Association as a Outdoor Decorative Ap-
pliance and should be installed according to these instructions.
Any alteration of the original design, installed other than as
shown in these instructions or use with a type of gas not
shown on the rating plate is the responsibility of the person
and company making the change.
Important
All correspondence should refer to complete Model Number, Serial
Number and type of gas.
Gas Inlet
Qualified Installing Agency
Installation and replacement of gas piping, gas utilization equipment
or accessories and repair and servicing of equipment shall be per-
formed only by a qualified agency. The term "qualified agency" means
any individual, firm, corporation or company which either in person
or through a representative is engaged in and is responsible for (a)
the installation or replacement of gas piping or (b) the connection,
installation, repair or servicing of equipment, who is experienced in
such work, familiar with all precautions required and has complied
with all the requirements of the authority having jurisdiction.
Commonwealth of Massachusetts: The installation must be
made by a licensed plumber or gas fitter in the Commonwealth
of Massachusetts.
The installation and the provisions for combustion and ventilation
air must conform with the National Fuel Gas Code, ANSI Z223.1/
NFPA54* Canadian Installation Code CAN/CGA B149.
*Available from the American National Standards Institute, Inc. 11
West 42nd St., New York, N.Y. 10018.
Page 8
INTRODUCTION

GENERAL INFORMATION

3/8" (9.5mm)
Cylinder valves shall be readily accessible for hand opera-
tion. A door on the enclosure to gain access to the cylinder
valves is acceptable, provided it is non-locking and can be
opened without the use of tools.
There shall be aminimum clearance of 2 inches (51 mm)
between the lower surface of the floor of the Propane Gas
supply cylinder enclosure and the ground.
The design of the appliance shall be such that (1) the
Propane Gas supply cylinder(s) can be connected, discon-
nected and the connections inspected and tested outside the
cylinder enclosure; and (2) those connections which could
be disturbed when installing the cylinder(s) in the enclosure
can be leak tested inside the enclosure;
High Altitude Installation
When installing this unit at an elevation above 2000 feet (in the
United States) it may be necessary to decrease the input rating by
changing the existing burner orifice to a smaller size. Generally,
input should be reduced 4 percent for each 1000 feet above sea
level. However, if the heating value of the gas has been reduced,
this general rule may not apply. Check with local gas utility for proper
orifice size identification.
For Canadian high altitude applications, this appliance is suitable for
installation at elevations between 0 feet (0m) and 4,500 (1,370m)
without change.
When installing this unit at an elevation above 4500 feet (1,370m)
(in Canada), check with local authorities.
Consult your local gas utility for assistance in determining the proper
orifice for location.