電話 Avaya EA401のPDF 設置および操作マニュアルをオンラインで閲覧またはダウンロードできます。Avaya EA401 20 ページ。 Avaya explosive atmosphere telephone installation & operation manual

Avaya Inc.
Declassify the hazardous location before proceeding with any
installation or electrical wiring.
Follow all appropriate electrical codes and use only approved electrical
fittings for the installation.
Choose a wall location that is free of obstructions and permits space for ½"
NPT conduit runs
Ensure mounting can support 16.5lbs. (7.5kg), plus the weight of any
peripheral equipment.
Ensure that none of the electrical connection circuits are live.
Use the template provided to locate and drill holes for mounting screws.
Use ¼" bolts or screws to mount the unit.
Secure the unit to the wall:
Attach lower conduit nipples to the telephone and ensure a minimum five
thread engagement.
Mount an approved explosion proof junction box within 45.7 cm (18") of the
telephone's lower sealing cavity and bring telephone wires into this box.