- ページ 14
ストレージ Dell SD630-SのPDF 配備マニュアルをオンラインで閲覧またはダウンロードできます。Dell SD630-S 31 ページ。 Designed for scality ring
Figure 6. Rack space—Dual Node
1.
Switches for management, application, and
storage networks
3.
One or more Dell SD630-S (Connector– file
server only)
Dell Storage Designed for Scality RING requires racks with a minimum depth of 1200 mm (48 inches).
Ensure that there is enough contiguous rack space in the rack for your solution, as shown in the
following table. The requirements listed in the table here do not include space for switches.
A minimum configuration has three Dell SD7000-S Dual Node or six Dell SD7000-S Single Node Physical
Servers, each requiring 4U of vertical rack space. You can add an additional Dell SD7000-S Physical
Server to expand the storage capacity of the Scality RING at any time.
NOTE: A 1200 mm rack (48 inches deep with a minimum of 130 mm extension) may be required to
accommodate power distribution units and cable management arms that are located internal to the
rack because the Dell SD7000-S (Single or Dual Node) Physical Storage Server is 1098.4 mm (43.2
inches) deep and fills the space extending from the front door to the back door.
NOTE: If a cable management arm is used, a minimum of 130 mm extension is required.
14
2.
Dell SD630-S (Supervisor)
4.
Minimum three Dell SD7000-S Dual Node