393803‐2 Startup procedure for EnSy AHU units
 
7. Verify that the signal from cooker hood / kitchen ventilator works. 
If a cooker hood is connected towards the ventilation unit it is important that there is signal from 
cooker hood into KV connection plug on the ventilation unit. 
This signal can be taken from the cooker hood directly or  via a pressure switch in the piping between 
cooker hood an ventilation unit. 
 
If a two‐step kitchen ventilator is used then it is important that in the first step, where only the 
damper opens, there also is signal from ventilator into KV connection plug on the ventilation unit. 
This signal can be taken from the cooker hood directly, if possible, or  via a pressure switch in the 
exhaust piping from the ventilator. 
 
Kitchen ventilator with integrated fan is not allowed to connect directly to the «Cooker hood» inlet 
on the ventilation unit. For this you need to make its own exhaust piping through wall. Anyway you 
need to make a signal from kitchen ventilator into KV connection plug on the ventilation unit. This 
signal can be taken from the kitchen ventilator directly, if possible, or  via a pressure switch in the 
exhaust piping from the ventilator. 
 
 
Inn all cases it is important to see that there are signal in display when activating any steps 
on cooker hood / ventilator.  
 
Do this signal show in display on all steps when activating cooker hood / ventilator.  
Yes or NO: ____________ 
 
If a pessure switch is used to get signal it is important thet it is adjusted with such a high value that it 
don't give signals when cooker hood / ventilator is not activated. 
We reserve the right to change technical data without notice     http://www.ensy.no 
This is important to avoid rotor alarm.
REV:0_08.09.2016. KJK 
 
 