- ページ 6

産業機器 Allmand MAXI HEAT 500IQのPDF マニュアルをオンラインで閲覧またはダウンロードできます。Allmand MAXI HEAT 500IQ 19 ページ。

SERIAL NUMBER 14-000001 AND UP 
Blower Fan Stops Circulating or gets a Red "X" over fan:
**MH 500 IQ has a burner that will start up and the fan will not turn on. Fan not running
will cause the unit to shut down ​ . **
❏ When this fault occurs it is an indication the fan is losing power.
❏ Check all the circuits to the fan. Power comes from 120 plug in into the bottom of
the IQ controller.
❏ Start with going to the IQ control box for the burner that is having the issue. Open
the cover of the box and over to the side is a wrench icon, press it. After pressing
the icon type the password 123 then press the​ Enter​ button. You can control the
fan manually from this point.
❏ Note: If you turn the fan on manually and the fan doesn't run, then the
motor for the fan could be faulty and need to be replaced (#107194)
❏ If the fan runs while in manual mode then the fan is working and power going to
fan is ok. The circuit into the IQ controller that controls the blower fan has a loose
or faulty connection.
❏ Check the red terminal block at the bottom of the IQ controller (See examples
below). 120 volts into the terminal block feeds the relay above it and into the fan
circuit during the purge process.
M axi Heat 500IQ