Allmand MAXI HEAT 500IQ 매뉴얼 - 페이지 6
{카테고리_이름} Allmand MAXI HEAT 500IQ에 대한 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Allmand MAXI HEAT 500IQ 19 페이지.
SERIAL NUMBER 14-000001 AND UP
Blower Fan Stops Circulating or gets a Red "X" over fan:
**MH 500 IQ has a burner that will start up and the fan will not turn on. Fan not running
will cause the unit to shut down . **
❏ When this fault occurs it is an indication the fan is losing power.
❏ Check all the circuits to the fan. Power comes from 120 plug in into the bottom of
the IQ controller.
❏ Start with going to the IQ control box for the burner that is having the issue. Open
the cover of the box and over to the side is a wrench icon, press it. After pressing
the icon type the password 123 then press the Enter button. You can control the
fan manually from this point.
❏ Note: If you turn the fan on manually and the fan doesn't run, then the
motor for the fan could be faulty and need to be replaced (#107194)
❏ If the fan runs while in manual mode then the fan is working and power going to
fan is ok. The circuit into the IQ controller that controls the blower fan has a loose
or faulty connection.
❏ Check the red terminal block at the bottom of the IQ controller (See examples
below). 120 volts into the terminal block feeds the relay above it and into the fan
circuit during the purge process.
M axi Heat 500IQ