Default I/O connection diagram
Notes:
*Total maximum current: 200
mA
Wire sizes and tightening
torques:
2
X2: 0.5 ... 2.5 mm
(24...12
AWG). Torque: 0.5 N·m (5 lbf·in)
X3, X4, X5, X6:
2
0.5 ... 1.5 mm
(28...14 AWG).
Torque: 0.3 N·m (3 lbf·in)
1) WFU-xx cooling fan control
2) WFU-xx temperature
supervision
Order of terminal
headers and jumpers
X1 (2-pole)
X2 (3-pole)
X3 (4 × 4-pole,
1 × 3-pole)
X4 (1 × 7-pole,
1 × 2-pole,
1 × 3-pole)
J1
J2
J3
X5 (3-pole)
X6 (4-pole,
orange)
Quick installation and start-up guide – ACSM1-204 9
X1
External power input
24 V DC, 1.6 A
X2
Relay output
250 V AC / 30 V DC
2 A
X3
+24 V DC*
Digital I/O ground
Digital input 1: Stop/start (EXT2)
Digital input 2: EXT1/EXT2
+24 V DC*
Digital I/O ground
Digital input 3: Fault reset
Digital input 4: Force stop
+24 V DC*
Digital I/O ground
Digital input 5: Not connected
Digital input 6: Not connected
+24 V DC*
Digital I/O ground
Digital I/O 1: Fan control signal (output) DIO1
Digital I/O 2: Running (output)
+24 V DC*
Digital I/O ground
Digital I/O 3: Fault (output)
X4
Reference voltage (+)
Reference voltage (–)
Ground
Analogue input 1: Not connected
Analogue input 2: Not connected
AI1 current/voltage selection
AI2 current/voltage selection
Thermistor input
Ground
Analogue output 1 (current)
Analogue output 2 (voltage)
Ground
X5
Drive-to-drive link termination
Drive-to-drive link.
X6
Not in use. Both circuits must be closed
with jumpers for the regen supply
module to start.
Control panel connection
Memory unit connection
+24VI
1
GND
2
NO
1
COM
2
NC
3
+24VD
1
DGND
2
DI1
3
DI2
4
+24VD
5
DGND
6
DI3
7
DI4
8
+24VD
9
DGND
10
DI5
11
DI6
12
+24VD
13
DGND
14
15
DIO2
16
+24VD
17
DGND
18
DIO3
19
24 V DC
+VREF
1
-VREF
2
AGND
3
AI1+
4
AI1-
5
AI2+
6
AI2-
7
J1
J2
TH
8
AGND
9
AO1 (I)
10
AO2 (U)
11
AGND
12
J3
B
1
A
2
BGND
3
OUT1
1
OUT2
2
IN1
3
IN2
4
X7
X20
1
WFU
X3.14
X3.15
2
WFU
X4.8
X4.9