10 Quick installation and start-up guide – ACSM1-204
Default connections
Make the following connections on the control unit before attempting to start up the
regen supply module:
• X3:14, 15 Fan control signal. The fan control cable must be connected.
Note: A 24 V DC supply must be connected to the WFU-xx filter.
• X4:8, 9 Thermistor input. The filter temperature monitoring cable must be
connected.
• X6:1, 3 and X6:2, 4 Not in use. Both circuits must be closed with jumpers
(included in delivery).
Connection procedure
The clamp plate can be fastened at the top or the bottom of the JCU Control Unit.
0.7 N·m
(6.2 lbf·in)
Use shrink
tubing or tape to
contain strands
If shielded
cable is in use,
remove outer
jacket of cable
at clamp to
expose cable
shield.
1.5 N·m
(13 lbf·in)